1234567891011121314151617181920212223242526272829303132333435363738394041424344454647 |
- # you can disable an alarm notification by setting the 'to' line to: silent
- template: nut_10min_ups_load
- on: nut.load
- class: Utilization
- type: Power Supply
- component: UPS
- os: *
- hosts: *
- lookup: average -10m unaligned of load
- units: %
- every: 1m
- warn: $this > (($status >= $WARNING) ? (70) : (80))
- crit: $this > (($status == $CRITICAL) ? (85) : (95))
- delay: down 10m multiplier 1.5 max 1h
- info: average UPS load over the last 10 minutes
- to: sitemgr
- template: nut_ups_charge
- on: nut.charge
- class: Errors
- type: Power Supply
- component: UPS
- os: *
- hosts: *
- lookup: average -60s unaligned of battery_charge
- units: %
- every: 60s
- warn: $this < 75
- crit: $this < 40
- delay: down 10m multiplier 1.5 max 1h
- info: average UPS charge over the last minute
- to: sitemgr
- template: nut_last_collected_secs
- on: nut.load
- class: Latency
- type: Power Supply
- component: UPS device
- calc: $now - $last_collected_t
- every: 10s
- units: seconds ago
- warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
- crit: $this > (($status == $CRITICAL) ? ($update_every) : (60 * $update_every))
- delay: down 5m multiplier 1.5 max 1h
- info: number of seconds since the last successful data collection
- to: sitemgr
|